UKOOA TYPE KG / TYPE KJ 150/250V Flame Retardant

Application

These cables are designed for fixed installation for control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.

Standards

  • BS 6883/BS 7917/UKOOA
  • IEC 60332-3-22 CAT. A
  • IEC 60332-1
  • IEC 60754-1 & IEC 60754-2
  • IEC 61034-1 & IEC 61034-2

Construction

Conductors Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228.
Insulation EPR complying with BS7655 GP4
Drain Wire Tinned copper drain wire
Collective Screen Aluminium mylar tape screen
Bedding EVA - SW4 compound complying with BS 7655
Armour Galvanised steel wire braid to BS 6883
Outer Sheath EVA - SW4 compound complying with BS 7655 (TYPE KG: Blue; TYPE KJ: Grey).

Dimensions and Weight

Construction
No. of cores×Cross section(mm^2)
Nominal Insulation Thickness
mm
Nominal Thickness of Inner Sheath
mm
Nominal Thickness of Outer Sheath
mm
Nominal Overall Diameter
mm
Approx. Weight
kg/km
1×2×0.75 0.8 1.2 1.25 12.9 200
3×2×0.75 0.8 1.2 1.4 17.9 468
7×2×0.75 0.8 1.4 1.7 22.4 706
12×2×0.75 0.8 1.6 1.7 28.0 1030
20×2×0.75 0.8 1.8 2.0 35.2 1662
1×3×0.75 0.8 1.0 1.25 13.5 285
3×3×0.75 0.8 1.3 1.2 20.4 680
7×3×0.75 0.8 1.5 1.4 26.0 1325
12×3×0.75 0.8 1.7 1.7 34.6 2106
1×2×1.0 0.8 1.0 1.0 13.4 180
1×3×1.0 0.8 1.1 1.1 14.0 300
1×4×1.0 0.8 1.1 1.2 15.0 180
1×2×1.5 0.8 1.1 1.2 13.5 297
3×2×1.5 0.8 1.3 1.4 19.8 593
7×2×1.5 0.8 1.4 1.6 25.0 929
12×2×1.5 0.8 1.7 1.9 32.6 1510
20×2×1.5 0.8 1.9 2.1 39.9 2287
1×3×1.5 0.8 1.1 1.2 14.0 304
3×3×1.5 0.8 1.3 1.5 23.7 760
7×3×1.5 0.8 1.5 1.7 30.5 1262
12×3×1.5 0.8 1.8 2.0 40.7 2148
1×2×2.5 0.8 1.1 1.2 15.1 320